Overview

The Hannibal PL-1P-50...100KVA is a single-phase industrial UPS listing range for industrial facilities, control rooms, utilities and medium-size 230VAC critical loads. It targets engineers and buyers searching for a transformer-based industrial UPS, online UPS system, backup power supply and critical power protection system for industrial environments.

This PL Series configuration uses SCR/IGBT technology with proven digital control and an IGBT inverter bridge with output isolation transformer. It is built for 230VAC and 110VAC output applications, with static bypass transfer below 4 ms, front-access maintainability, battery autonomy on request and communication options for remote supervision.

SEO content for this page should connect the model range with high-intent terms such as industrial UPS, online double-conversion UPS, transformer-based UPS, critical power UPS, power backup for industrial plants and UPS for process industries.

Key features

  • Single-Phase PL Series UPS, 50-100 kVA, aligned with the brochure-backed PL Series range.
  • Online UPS architecture for backup power, voltage stabilization and protection from spikes, drops and outages.
  • SCR/IGBT technology with proven digital control for industrial reliability and configurable system design.
  • IGBT inverter bridge with output galvanic separation transformer, preventing DC component on the output.
  • Built-in static and manual bypass with LCD/HMI support for high availability and easier operation.
  • Streamlined cooling design reduces operating temperature of critical components.
  • True front access to replaceable components helps reduce MTTR and simplify service work.
  • Smart Parallel Switching supports dynamic control of paralleled systems for redundancy and availability.
  • Transformer-based industrial inverter design improves robustness, endurance and noise filtering.
  • Custom options are available for rectifier charger, battery line, system, bypass line, communication and mechanical requirements.

Technical specifications

Technical specifications for PL-1P-50...100KVA
Product categoryIndustrial Uninterruptible Power Supply (UPS), PL Series
Power range50-100 kVA
Technology platformSCR/IGBT technology with proven digital control
AC input voltage110 / 120 / 200 / 220 / 240 / 277 V
Input voltage tolerance+/- 15%
Input frequency50 Hz (60 Hz available)
Rectifier topologyThyristor 6-pulse standard; thyristor 12-pulse optional; IGBT rectifier optional
Input THD<30% for 6-pulse rectifier; <12% for 12-pulse version
Input power factor0.8
Battery typeLead-acid or nickel-cadmium, vented or recombination
AutonomyFrom a few minutes to several hours, on request
Battery current limitation0.1C lead-acid battery; 0.2C nickel-cadmium battery
Battery ripple<5% for single-phase UPS
AC output voltage1 x 230 V (220 / 240) or 1 x 110 V (115 / 120), other options on request
Inverter topologyIGBT with output isolation transformer
AC voltage tolerance1%
Output frequency50 Hz (60 Hz available)
Frequency tolerance+/- 0.05%
Overload capability150% of nominal power for 1 minute; 125% for 10 minutes
Output harmonic distortion<3% with 100% linear load; <5% with 100% non-linear load
Output power factor0.8 / 0.9
Allowable crest factorUp to 3:1
Short-circuit clearance250% / 100 ms - 175% / 5 s
Static transfer switchSCR type, static bypass transfer time <4 ms
Maintenance bypassIsolator
Operating temperature0 to 40 deg C
CoolingForced fan cooling; free cooling optional
ProtectionIP20 standard according to IEC 60529
CommunicationRTU RS485 standard; TCP/IP optional
Touch panel HMIStandard

Applications

  • Industrial control rooms and automation panels.
  • Manufacturing and process lines.
  • Transport and infrastructure systems.
  • Single-phase critical AC loads.
  • Backup power where stable AC output is required.