Skip to content
Hannibal Power & Technology
Enquire

HR Series · Three-phase

110V DC Three-Phase Battery Charger for Substation & Switchgear (10A–2500A)

HR-3P-110V-10…2500A

The Hannibal HR-3P-110V is a three-phase 110VDC battery charger and rectifier rated from 10A to 2500A, engineered to provide high-reliability power supply and battery charging for substations and switchgear.

Industrial Rectifier
Nominal DC output
110 VDC
Input voltage (AC)
3 x 400V (380 / 415V)
Charge modes
Float, Equalize, Boost (auto & manual)
DC voltage range
88–160 VDC
Redundancy
Dual DC UPS / dual charger, DC load sharing
Communication
RS232 / RS485, Modbus RTU, Modbus/TCP-IP

Overview

The Hannibal HR-3P-110V is a three-phase 110VDC battery charger and rectifier rated from 10A to 2500A, engineered to provide high-reliability power supply and battery charging for substations and switchgear. It feeds the protection relays, SCADA, control and tripping circuits of electrical substations and, combined with a stand-by battery, guarantees power backup for substations, SCADA and switchgear even during a total AC outage.

Three-phase input and 6-pulse (B6C) or 12-pulse (B12C) thyristor-controlled topologies with DSP control deliver high power with low THDi, while a galvanic isolation transformer holds voltage regulation and output ripple below 1%. Earth leakage monitoring (OPS-02), DC earth fault detection and transducers with 0–10V / 4–20mA outputs (OPS-11) provide complete supervision, and dual DC UPS / dual battery charger arrangements with DC load sharing deliver the redundancy that transmission and distribution networks demand.

Key features

  • Three-phase 110VDC output, 10A to 2500A, for substation and switchgear DC systems.
  • Supplies protection relays, SCADA, control and tripping circuits with constant-current operation under load.
  • 6-pulse (B6C) and 12-pulse (B12C) thyristor-controlled topologies with DSP control and low THDi.
  • Galvanic isolation transformer, voltage regulation < 1% and output ripple < 1%.
  • Earth leakage monitoring (OPS-02) and DC earth fault detection for network protection.
  • Transducers 0–10V / 4–20mA (OPS-11) and dry contact alarm relays for full supervision.
  • Dual DC UPS / dual battery charger with DC load sharing for utility-grade redundancy.
  • RS232 / RS485 Modbus RTU and Modbus / TCP-IP communication.

Technical specification

Input specifications for HR-3P-110V-10…2500A
Input voltage (AC)3 x 400V (380 / 415V)

Applications

  • High-voltage and distribution substations.
  • Switchgear and protection & control systems.
  • Power transmission and distribution networks.
  • SCADA and grid-automation systems.
  • Power generation and water treatment plants.

Options, standards & platform

Battery compatibility

HR Series chargers are fully compatible with sealed and vented batteries across all major chemistries, with intelligent battery management and temperature compensation to extend service life:

  1. Maintenance-free and vented: OPzS, OPzV, VRLA (valve-regulated), Gel and AGM lead-acid.
  2. Nickel-Cadmium (Ni-Cd) — vented and recombination types.
  3. Lithium-Ion (Li-Ion), Calcium-Ion and Sodium-Ion advanced chemistries.
  4. Battery monitoring system (Hannibal BMS), DC earth fault detection and battery room temperature sensor options.
  5. Compatible with leading battery brands including EnerSys and Exide.
Options & accessories
  1. Alarm & communication interface
  2. Earth leakage monitoring
  3. Gauges for analog measurements.
  4. Output breaker / load dropper module
  5. Battery temperature compensation
  6. Input power measurement.
  7. Transducers (0–10V, 4–20mA)
  8. Active parallel current sharing
  9. Fast-acting semiconductor fuses
  10. Fan failure monitoring.
  11. 12-pulse operation option, IGBT rectifier, harmonic filter, DC shock / DC filter and one-to-four-step dropper diode voltage regulation.
  12. Outdoor equipment and ingress protection: IP42, IP54, IP55 and IP65, with altitude operation up to 2000m and natural cooling on request.
  13. H2S gas compensation for geothermal power plants and the petrochemical industry; anti-seismic design for high-vibration sites.
Standards & compliance
  1. IEC 60146-1-1 / IEC/NF EN 60146-1-1 — Semiconductor converters (basic requirements).
  2. IEC 61204-1, IEC 62040-2 (EMC), IEC 60335 — power supply and safety standards.
  3. ISO 9001, ISO 14001, ISO 27001 management system certifications.
  4. CE marked, compliant with EMC and Low Voltage directives.
  5. Total harmonic distortion (THDi) controlled via 6-pulse, 12-pulse and IGBT topologies; harmonic filter available.
WhatsApp